OSES THREE PHASE OPERATOR MANUAL - EN
Issue No: AE/OSES-3P/TP/07/2011
- Page 5 of 37-
Being able to accommodate an input voltage swing in excess of 40%, whilst still delivering
accuracy on the output of 1% or better, the Servo Electronic design principle comprises a
transformer having its secondary winding connected between the mains supply and the load.
The primary voltage is automatically controlled through a servo motor driven variable
transformer, thereby ensuring a continuous, smooth and very stable output voltage.
A solid state Servo-Amplifier continuously monitors the output voltage of the stabiliser.
Should, due to an incoming voltage or load current change, the output voltage deviate from
the required value, the Amplifier sensor instructs the servo motor to rotate the brush-gear on
the variable transformer to correct the output for the deviation. The speed of detection and
actions of the servo system are exceptionally fast, with controlled motor deceleration to
minimise any possibility of overshoot.
Over the years with advances in semi-conductor, motor and digital technologies, our
development engineers have considerably enhanced the performance of the basic design
principle. Our latest Servo Electronic generation of solutions deliver the most reliable, fastest
acting, highly stable and most energy efficient operation seen in the market today.
For details on the Technical Specification of the OSES Range of Three Phase Outdoor
AC Automatic Voltage Stabilisers see Section 10.1 in the Appendix to this manual.
For General Circuit Diagrams on the OSES Three Phase AC Voltage Stabilisers,
please refer –
For 4 Wire OSES Three Phase Stabilisers – H & LY Series – see Section 12.3 in
the Appendix to this manual
For 3 Wire OSES Three Phase Stabiliser – HD & LD Series – see Section 12.4 in
the Appendix to this manual.