ASHLEY-EDISON (UK)
Manufacturers of Voltage Stabilisers – Power Conditioners – Constant Voltage Compensators – Variable Transformers
OSES THREE PHASE OPERATOR MANUAL - EN
Issue No: AE/OSES-3P/TP/07/2011
- Page 27 of 37-
12. APPENDIX
12.1 TECHNICAL SPECIFICATION
Input Voltage:
See Label on the Unit
Output Voltage:
See Label on the Unit
Output Voltage Accuracy:
±0.5% (H & LY Series) ±1% (HD & LD Series)
Frequency:
47 to 65Hz
Response Time:
<1.5ms
Correction Time:
A 10% supply variation will be corrected to within 2.5% in 0.6
seconds
Efficiency:
98%
Total Harmonic Distortion:
<1%
Soft Switch-ON:
This feature ensure that the output voltage is at its minimum
upon Switch-On before it commence full stabilisation
Power Factor:
Any lagging to 0.95 leading
10 x max current rating for 2 second
3 x max current rating for 1 minute
Surge Ratings:
2 x max current rating for 5 minutes
Surge Suppression:
Protects loads against high-energy spike and transient Voltages
Independent Phase Control:
Maintain each phase voltage irrespective of load unbalance
Environment:
Temperature range -15 to 50°C. Derate by 2% for each
additional °C up to max 60 °C.
Construction:
Enclosures to IP54, BS EN5490/IEC60529, NEMA 3
Conformance:
BS EN50081-1;2 / IEC 61000-4-3;4
CE Conformity:
EN55022, EN50082, ENV50140-1
Standard Features:
Input Circuit Breaker
Bypass Control Switch
Over/Under Voltage Trip Protection
Phase-Failure Trip Protection
Voltmeter / Selector Switch (internal)
Lightning Arrestor