ASHLEY-EDISON (UK)
Manufacturers of Voltage Stabilisers – Power Conditioners – Constant Voltage Compensators – Variable Transformers
OSES THREE PHASE OPERATOR MANUAL - EN
Issue No: AE/OSES-3P/TP/07/2011
- Page 20 of 37-
VR Adjustment Indicators Feature
Clockwise LED3, Hi light “ ON ”
L1 phase voltage increase
VR1
Anti-Clockwise LED2, Low light “ ON ”
L1 phase voltage decrease
Clockwise LED5, Hi light “ ON ”
L2 phase voltage increase
VR2
Anti-Clockwise LED4, Low light “ ON “
L2 phase voltage decrease
Clockwise LED7, Hi light “ ON ”
L3 phase voltage increase
VR3
Anti-Clockwise LED6, Low light “ ON “
L3 phase voltage decrease
9.2.1 FOR 4 WIRE SOLUTIONS (H & LY SERIES)
Measure the ‘Neutral’ to output voltage and adjust each line as required.
Example, place the first meter probe on the output ‘Neutral’ and the other meter
probe on the output ‘L1 Phase’ - adjust pot ‘VR1’, until the voltage meets the
required value.
Continue with the other two output phases - L2 & L3 - with the first probe still on the
‘Neutral’, the other probe on the relevant output phase and adjustments being made
to relevant phase pot on the Servo Amplifier PCB.
9.2.2 FOR 3 WIRE SOLUTIONS (HD & LD SERIES)
Measure the ‘output voltage Line to Line ie. L1 to L2 and adjust as required.
Example, place the first meter probe on the output ‘L1 Phase’ and the other meter
probe on the output ‘L2 Phase’ - adjust pot ‘VR1’, until the voltage meets the
required value.
Continue accordingly with the other two output phases - L2 to L3 and L3 to L1 with
adjustments being made to relevant phase pot on the Servo Amplifier PCB.
9.3 OVER / UNDER VOLTAGE & PHASE FAILURE PROTECTION
SW1 Switch on the Servo Amplifier PCB activates the Over / Under Voltage & Phase
Failure Protection features.
By default these protection features are deactivated.
With activation, should the outgoing voltage from the Stabiliser drift, other than
momentarily, by 15% or more, the Stabiliser’s input circuit breaker will automatically
trip – thereby protecting the load.
To minimise the possibility of nuisance tripping, this setting is set by default at 15%.
If required, the sensitivity setting can be recalibrated to 9% – please refer to the
Ashley-Edison Service Department for guidance. However, in the interest of ease
for all, it is normally recommended that the machine be supplied already pre-
calibrated by our factory engineers for the lower setting.