Ashley-Edison M2 Bedienungsanleitung Seite 22

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 37
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 21
ASHLEY-EDISON (UK)
Manufacturers of Voltage Stabilisers – Power Conditioners – Constant Voltage Compensators – Variable Transformers
OSES THREE PHASE OPERATOR MANUAL - EN
Issue No: AE/OSES-3P/TP/07/2011
- Page 22 of 37-
Basic maintenance procedures should include –
Visual Inspection
Check to ensure that there are no obvious signs of
damage to any of the components in the system. Check
all wiring connections to ensure none have worked
loose. As required, tighten any loose connections. Check
the cooling fans to ensure they are rotating freely.
Cleaning
Ensure the Stabiliser is kept free from dust and dirt. Blow
out any dust or dirt ideally with compressed air or
alternatively remove with a soft brush.
Carbon Brush Inspection
Ensure that the tips on the variable transformers carbon
brushes are at least 1mm in thickness.
WARNING!
Do not attempt to
manually force the Brush
Gear and associated
Carbon Brushes to
rotate. Rotation will
damage the Servo Motor
and associated Brush
Gear.
If 1mm, or less, replace the carbon brush.
Ideally spare carbon brushes should be held on site – see
Section 10.3 – Recommended Spares below.
Output Voltage
Adjustment
Upon repowering the machine, check the output voltage
settings. If necessary, adjust the output voltage – as described
in
Section 9 – Output Voltage Adjustment in this manual.
1 mm
Seitenansicht 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 36 37

Kommentare zu diesen Handbüchern

Keine Kommentare